드라고 신호변환기      DRAGO Signal Converters

측정, 제어, 자동화를 위한 산업용 신호처리, DRAGO가 합니다.

페이지

Homepage

제품군

Product Line

제품소개

Products

신호변환기 선정 가이드

Selection Matrix

제품 전체 보기

Service Web Portals

내려받기

Downloads

제품 및 구입 문의

Contact

Current Monitoring Relay DG 35300
Current Monitoring Relay DG 35300

 

  • Input for current measurement and mV shunt voltage
    using internal or external shunt resistor
  • Easy configurable via DIP switches or via USB
    limit point, hysteresis and mode of operation can be directly set, limit point adjust
  • Switchable timer and special functions
    Switch-on delay, switch-off delay and wiper function, Memory and window functions
  • 3-Port-Separation
    protection against switching errors due to parasitic voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector
    allows for fast and economical installation
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • 5 Years Warranty
    Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)

DG35300 초슬림형 전류 감시 알람 릴레이 / 오픈컬렉터
Current Monitoring Relay DG 35300

DC 및 AC 전류 신호 모니터링

설정 가능한 전류 모니터링 릴레이 DG 35300은 션트저항으로 전류 측정을 위해 DC 및 AC 전류 및 mV 신호의 제한 모니터링 및 처리에 사용됩니다. SPST 릴레이 또는 선택적으로 절연 된 수동 트랜지스터 스위치 (Open-Collector)가 출력에서 ​​사용 가능합니다.

The configurable Current Monitoring Relay DG 35300 is used for limit monitoring and processing of DC and AC current signals and mV signals for current measuring with shunt resistors. A SPST relay or optionally an isolated, passive transistor switch (Open-Collector) is available at the output.

입력

0 ~ 5A AC/DC     0 ~ 150mV AC/DC

릴레이 출력
(DG353
00)

250V AC  /  30V DC  /  2A

오픈컬렉터 출력
(DG353
80)

36V DC  /  50mA

전원

24V DC (전원 배선 Bus 단자 옵션)

특징 

전류(AC/DC) 한계값 모니터링 및 알람 출력
DIP 스위치 또는 PC에서 입력/출력 설정 및 변경
두께 6.2mm 초슬림형

  • 전류 측정 및 mV 션트 전압 입력
    내부 또는 외부 션트 저항 사용
  • DIP 스위치 또는 USB를 통해 손쉽게 설정 가능
    한계점, H
    ysteresis 및 작동 모드를 직접 설정할 수 있으며, 한계점 조정
  • 전환 가능한 타이머 및 특수 기능
    Switch-on 지연, Switch-off 지연 및 Wiper 기능, 메모리 및 Window 기능
  • 3-Port 분리
    기부유
    전압(S
    tray Voltage) 또는 접지루프(Ground Loop)로 인한 스위칭 오류 방지
  • 매우 슬림 한 디자인
    간단하고 공간 절약을 위한 6.2mm 슬림 하우징 DIN 레일 장착
  • 옵션 In-Rail-Bus 마운팅 레일 커넥터
    빠르고 경제적인 설치가 가능하다.
  • EN 61140 (KS C IEC 61140) 규격에 따른 감전보호
    허용되지 않는 고전압으로부터 서비스 요원 및 후속 장치를 보호합니다.
  • 5년 보증
    배송일로부터 5년 이내에 발생하는 결함은 무료로
    수리 또는 교환해 드립니다.

설정 가능한 전류 모니터링 계전기 DG 35300은 션트 저항으로 전류 측정을 위해 DC 및 AC 전류 신호 및 mV 신호의 제한 모니터링 및 처리에 사용됩니다. SPST 릴레이 또는 선택적으로 절연된 수동 트랜지스터 스위치 (Open-Collector)가 출력에서 사용 가능합니다.

전류 감시 릴레이는 MIN 및 MAX 경보에 대한 AC / DC 전류 신호 및 mV 신호를 모니터링하고 한계값 메시지를 스위칭 출력으로 전송합니다.

설정은 DIP 스위치 또는 전면 프로그래밍 인터페이스를 통해 수행됩니다 (DZU 1201 필요, 액세서리 참조). 모니터링 계전기는 조정 가능한 switch-on지연, switch-off 지연 및 wiper 기능을 갖추고 있습니다. latch 기능 및 window 기능과 같은 추가 설정도 가능합니다.

전원은 연결 단자 또는 옵션 In-Rail-Bus를 통해 공급할 수 있습니다 (액세서리 참조). 스위칭 상태와 장치 상태는 전면 패널의 LED로 표시됩니다. 장치가 In-Rail-Bus를 통해 작동하는 경우 그룹 메시지를 사용할 수 있습니다.

The configurable Current Monitoring Relay DG 35300 is used for limit monitoring and processing of DC and AC current signals and mV signals for current measuring with shunt resistors. A SPST relay or optionally an isolated, passive transistor switch (Open-Collector) is available at the output.

The Current Monitoring Relay monitors AC/DC current signals and mV signals for MIN and MAX Alarm and transmits the limit value message to the switching output.

The configuration is carried out via DIP switches or via the front programming interface (requires DZU 1201, see accessories). The monitoring relay has an adjustable switch-on delay, switch-off delay and a wiper function. Further settings such as latch function and window function are also possible.

Power can be supplied via the connection terminals or via the optional In-Rail-Connector (see accessories). The switching status and the device status are indicated by LEDs on the front panel. If the device is operated via the In-Rail Connector, a group message is available.

 

Technical Data

Input

 Current InputmV Input
Input signal1)
Monitoring range
0 to 5 A AC/DC
0 to 5500 mA
0 to 150 mV
0 to 165 mV
Input resistance0.01 Ω100 kΩ
Over load< 10 A (< 30 A for 1 s)< 30 V

 

Output

DG35300 Relay (SPST)250 V AC / 30 V DC / 2 A
Recommended minimum load 300 mW / 5 V / 5 mA
DG35380 Transistor (Open-Collector)36 V DC / 50 mA, Residual voltage < 1.5 V ated
not current limited
Switching functionsMake contact, break contact
Normal, Latch
Time functionOn delay:
Off, 1 s, 2 s, 3 s, 5 s, 10 s, 20 s, 30 s
Resonse time≤ 20 ms
Switch state indicatorYellow LED on front
Group messageSignal at In-Rail-Connector E (supply circuit) at device failure and alarm

 

General Data

Switching errorDC: < 0.2 % full scale
AC: < 0.5 % full scale
Temperature coefficient2)< 100 ppm/K
Test voltage3 kV AC, 50 Hz, 1 Min., Input against output against power supply/In-Rail-Connector
Working voltage3)
(Basic Insulation)
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection against electrical shock3)Protective Separation by reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply.
Ambient temperatureOperation
Transport and storage
–25 °C to +70 °C   (-13 to +158 °F)
–40 °C to +85 °C   (-40 to +185 °F)
Power supply24 V DC,     16.8 V to 31.2 V DC, max. 1.0 W
EMC4)EN 61326-1
Construction6.2 mm (0.244") housing, protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
WeightApprox. 70 g
  1. Factory setting: switching point = 3 A, hysteresis 10 %, MAX-alarm, normally open contact, time functions off
  2. Average TC in specified operating temperature range
  3. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipment’s. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  4. Minor deviations possible during interference

 

Block Diagram

Dimensions

DG35300

DG35300

 


Terminal assignments

1

+

Reset

2

+

mV input

3

GND

4

+

Current input

 

 

 

5

~

Relay

+

Transistor output

6

~

Relay

Transistor output

 

 

 

7

+

Power supply (connected to In-Rail-Bus D)

8

Power supply (connected to In-Rail-Bus C)

Connection
Captive plus-minus clamp screws
Wire cross-section 0.5 to 2.5 mm2 / AWG 20-14
Stripped length 8 mm / 0.3 in
Screw terminal torque 0.6 Nm / 5 lbf in
Optional power connection via In-Rail-Bus (see accessories)

 

 

제품 주문 코드   Order Codes

품목

주문번호

전류 모니터링 신호계전기
USB 인터페이스 또는 DIP 스위치를 이용하여
입출력
설정 가능

In-Rail-Bus (부속품 참조)

Current Monitoring Relay,
configuration via DIP switch or USB interface

 

 

나사(Screw) 단자

푸시인(Push-in) 단자

릴레이 출력
Relay Output

Bus 단자 무

DG 35300 S

DG 35304 S

Bus 단자 유

DG 35300 B

DG 35304 B

옵토커플러 (트랜지스터 스위치) 출력
Optocoupler (Trasister Switch Output)

Bus 단자 무

DG 35380 S

DG 35384 S

Bus 단자 유

DG 35380 B

DG 35384 B

 
여기에 표기된 사양들은 예고 없이 변경될 수 있습니다! (Specifications listed here are subject to change without notice!)
© Copyright 2004-2024 by DRAGO Automation GmbH

드라고 신호변환기 한국판매원 - 에이콤 (AKORM Corp.)